Advantech BB-WDR-240-24

SPHINX in Europe
IE
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • PL
  • ES
  • SE
  • CH
  • UK
Product groups > Power Supplies > Advantech BB-WDR-240-24

Advantech BB-WDR-240-24

240W, 24V, 10A, Single Output, Industrial DIN Rail Power Supply

Advantech BB-WDR-240-24
5998_18874.png
5998_18875.jpg
  • PropertiesProperties
  • DescriptionDescription
  • Further InformationFurther Information
  • PDFPDF
  • Single and two phase 180~550VAC wide input range
  • High efficiency 91% and low power dissipation
  • Protections: Short-circuit, Overload, Over-voltage, Over-temperature
  • Free air convection cooling
  • DIN rail TS-35/7.5 or 15 mountable
  • UL508 approved (industrial control equipment)
  • EN61000-6-2 (EN50082-2) industrial immunity level
  • Built-in DC OK relay contact
  • 100% full-load burn-in test
240W, 24V, 10A, Single Output, Industrial DIN Rail Power Supply
ProdGrafik

SPECIFICATIONS

MODEL BB-WDR-240-24
OUTPUT
DC VOLTAGE 24V
RATED CURRENT 10A
CURRENT RANGE 0 ~ 10A
RATED POWER 240W
RIPPLE & NOISE (max.) Note.2 150 mVp-p
VOLTAGE ADJ. RANGE 24 ~ 28V
VOLTAGE TOLERANCE Note.3 ± 1.0%
LINE REGULATION ± 0.5%
LOAD REGULATION ± 1.0%
SETUP, RISE TIME 800ms, 150ms/400VAC 1500ms, 150ms/230VAC at full load
HOLD UP TIME (Typ.) 18ms / 400VAC 18ms / 230VAC at full load
INPUT
VOLTAGE RANGE 180 ~ 550VAC        254 ~ 780VDC
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.) PF≥0.84/400VAC PF≥0.84/230VAC
EFFICIENCY (Typ.) 91% / 400V
AC CURRENT 1A/400VAC         2A/230VAC
INRUSH CURRENT (max.) COLD START 50A
LEAKAGE CURRENT <3.5mA / 530VAC
PROTECTION
OVERLOAD 105 ~ 130% rated output power
Protection type : Constant current limiting, unit will shut down after 3 sec. , auto-recovery after 1 minute if the fault condition is removed
OVER VOLTAGE 29 ~ 33V
Protection type : Shut down o/p voltage, auto-recovery after 1 minute if the fault condition is removed
OVER TEMPERATURE 90°C ± 5°C (TSW) detect on heatsink of power switch
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION
DC OK SIGNAL 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
ENVIRONMENT
WORKING TEMP. -30 ~ +70 °C (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85 °C, 10 ~ 95% RH
TEMP. COEFFICIENT ± 0.03%/ °C (0 ~ 50°C)
VIBRATION Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
SAFETY & EMC (Note 4)
SAFETY STANDARDS Ul508 approved, IEC60950-1 CB approved by SIQ, design refer to GL;(meet EN60204-1)
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 °C/ 70% RH
EMC EMISSION Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A approved
OTHERS
MTBF 141.1K hrs min MIL-HDBK-217F (25 °C)
DIMENSION 63*125.2*113.5mm (W*H*D)
PACKING 1.06Kg; 12pcs/13.7Kg/1.06CUFT
NOTE
    1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 °C of ambient temperature.
    2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
    3. Tolerance : includes set up tolerance, line regulation and load regulation.
    4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
    5. Installation clearances : 40mmon the top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In Case the adjacent device is a heat source, 15mm clearance is recommended.
    6. Derating may be needed under low input voltage. Please check the derating curve for more details.